Fuse Ratings
Part No.
Fuse Amps
Size
Average @50KA/500Vdc
Power Loss (W)
A²s Melting
A²t Clearing
100%
GFEVT500-100K-51E
100
1#
820
7,370
23
GFEVT500-125K-51E
125
1#
1,340
11,910
28
GFEVT500-160K-51E
160
1#
2,410
21,550
35
GFEVT500-200K-51E
200
1#
3,030
26,910
38
GFEVT500-250K-51E
250
1#
5,050
45,680
52
GFEVT500-275K-51E
275
1#
6,140
59,220
55
GFEVT500-315K-51E
315
1#
7,910
75,060
64
GFEVT500-350K-51E
350
1#
10,520
100,260
68
GFEVT500-400K-51E
400
1#
15,060
143,820
72
GFEVT500-450K-51E
450
1#
20,830
205,160
78
GFEVT500-500K-51E
500
1#
26,760
264,150
87
GFEVT500-550K-51E
550
1#
36,520
363,150
92
GFEVT500-630K-51E
630
1#
53,800
554,220
100
GFEVT500-700K-51E
700
1#
71,550
742,770
102
GFEVT500-800K-51E
800
1#
99,540
1,035,000
113