Higher Voltage Rating: Provides overall system efficiency using smaller, more economical conductors while meeting the needs of higher voltage.
Fast Fault Response: Up to ten times faster opening under high fault current conditions ensures reliable protection of circuits and components.
High Ampacity: Greater ampacity within sizing guidelines.
Durability: Excellent resistance to voltaic impingement and environmental temperature tolerance.
Robust Design: Exceptional resistance to mechanical vibration and impact resistance.
Fuse Ratings
Part No.
Fuse
Size
Average @ 50KA/1000Vdc
Power Loss (W) 1.0In
Amps
A²s Melting
A²s Clearing
GFEVT1000-50A-43E
50
01*
137
1,000
16
GFEVT1000-63A-43E
63
01*
215
1,620
19
GFEVT1000-80A-43E
80
01*
410
3,145
23
GFEVT1000-100A-43E
100
01*
740
5,645
29
GFEVT1000-125A-43E
125
01*
1,460
10,860
34
GFEVT1000-160A-43E
160
01*
2,535
19,850
41
GFEVT1000-200A-43E
200
01*
5,070
38,200
46
GFEVT1000-250A-43E
250
01*
8,970
68,550
51
GFEVT1000-315A-43E
315
01*
18,200
142,950
61
GFEVT1000-350A-43E
350
01*
26,400
199,500
66
GFEVT1000-400A-43E
400
01*
38,750
293,500
74
*:If there are any requirements, please communicate with the original factory staff first. Optional base indicator, the standard product is the “Default” configuration. Default: A–with fuse indication, e.g.: GFEVT1000-400A-43E; Optional: AN–without fuse indication, e.g.: GFEVT1000-400AN-43E;